MTP MPO Type B OM2 Multimode Fiber Optic Cable LSZH 12 Fiber
12FIBER MTP / MPO OM2 MULTIMODE FIBER OPTIC CABLE
The MPO/MTP Trunk cable is designs for Data Center Applications. It is divided into round cable and flat cable with the outer diameter of 3.0 mm or 4.5 mm. The connector where this cable is terminated on is the so called MPO/MTP connector. MPO/MTP Trunk Cable are factory pre-terminated, tested and packed along with the test reports. Available in 12 core configuration, these space saving assemblies comes with either MTP Male or MTP Female Connectors on both the other end. They are available in lengths of 5, 10, 20, 50, 100 meters, custom lengths are available on request. MPO/MTP Trunk Cables are available in Single mode, Multimode OM1, OM2, OM3 or OM4 with LSZH or PVC Jackets.
Features of MM OM4 MPO-MPO Patch Cord
• Factory-terminated provide consistent quality, high performance and reduce installation time
• 100% tested for low insertion loss performance and high back reflection
• Fiber Count: 12 fiber trunk cable
• Laser-Optimized multimode OM4 fiber
• Type B polarity, used for 40G QSFP eSR4 and 100G QSFP28 SR4 optics
• Optimized performance – available in elite MTP and discrete premium connector upon request
• Each MPO connector is polished according the polished end-face quality specification standard
• Easy connection and disconnection
Applications of 12F MPO to MPO Trunk Cable
Fiber Network Deployments
Fast Ethernet
Gigabit Ethernet
Other Data Applications Requiring High Transfer Rates
Specification of OM2 12 Core MPO-MPO Trunk Cable
Connector Dimensions: 7.75 mm height x 61 mm depth
Jacket material: PVC/LSZH
Jacket OD: 3.0 mm
Installation Tensile Load: 100 N (445 lbs)
Long-Term Tensile Load: 50 N (222 lbs)
Installation Minimum Bend Radius: 4.5 cm (1.8 in)
Long-Term Minimum Bend Radius: 3.0 cm (1.2 in)
Attenuation at 850 nm: 3.5 dB/km
Attenuation at 1300 nm: 1.0 dB/km
Maximum Connector Loss: 0.70 dB
Typical Return Loss: -22 dB
Operating Temperature: -20°C to +70°C
Please Note: Attenuation testing performed in accordance with EIA/TIA-455-171A.
Geometry Parameters
Measurement
Pass/Fail Limits
Parameters
Min
Max
Radius of Curvature
Long Axel
2000nm
∞
Short Axel
50mm
∞
Angle
Long Axel
-0.2°
0.2°
Short Axel
APC
7.8°
8.2°
PC
-0.2°
0.2°
Fiber Height
1000nm
3000nm
Different Fiber Height
N/A
500nm
Adjacent Fiber Height
N/A
300nm
Ferrule Length
7.9mm
N/A
Optical Performance
Optical Performance
Item
Parameters
MTP/MPO Connector
SM (1310nm/1550nm)
MM (850nm)
Standard
Low Loss
Standard
Low Loss
Insertion Loss
Typical
0.50dB
0.20dB
0.50dB
0.20dB
Maximum
0.70dB
0.35dB
0.70dB
0.35dB
Return Loss
≥60dB for APC
≥20dB for PC
≥40dB for PC
--
Male/Female
Male: with Pins, Female: without Pins